Server Technology switched pro2 User Manual page 163

Hide thumbs Also See for switched pro2:
Table of Contents

Advertisement

set line
Sets line configuration values.
Command Syntax
set line email [disabled | enabled] <name | id | ALL>
set line load [alarmhi | alarmlo | warnhi | warnlo] <name | id | ALL> <value>
set line load hyst <value>
set line snmpt [disabled | enabled] <name | id | ALL>
Parameters
The set line command uses the following parameters:
Sub-Parameters
The set line command uses the following sub-parameters:
min <= alarmlo <= warnlo <= warnhi <= alarmhi <= max
Command Access
Admin level only
set loadshed
Sets Smart Load Shedding configuration values.
Command Syntax
set loadshed branch [disabled | enabled]
set loadshed line [disabled | enabled]
set loadshed sensor [disabled | enabled]
set loadshed sensor contact [recoveroff | recoveron] <contact sensor name | id | ALL>
set loadshed sensor temp [recoveroff | recoveron] <temp sensor name | id | ALL>
set loadshed sensor water [recoveroff | recoveron] <water sensor name | id | ALL>
set loadshed ups [all | any] <line name | id | ALL>
set loadshed ups [disabled | enabled]
set loadshed ups [recoveroff | recoveron]
set loadshed ups [recoverdelay | sheddelay] <delay>
Using the Command Line Interface (CLI)
Email
Email notification for line events.
Hyst
Hysteresis between event state and recovery.
Load
Current load for a line. min = 0A, max (current limit) in show lines
command, hyst 0.0-10.0A (default 1.0A).
SNMPT
SNMP trap notifications for line events.
alarmhi
High alarm value.
alarmlo
Low alarm value.
warnhi
High warning alarm.
warnlo
Low warning alarm.