set cord
Sets cord configuration values.
Command Syntax
set cord email [disabled | enabled] <name | id | ALL>
set cord loadmax <name | id | ALL> <value>
set cord name <name | id> <name string>
set cord nomvolts <name | id | ALL> <value>
set cord outofbal [alarmhi | warnhi] <name | id | ALL> <value>
set cord outofbal hyst <value>
set cord pf [alarmlo | warnlo] <name | id | ALL> <value>
set cord pf hyst <value>
set cord snmpt [disabled | enabled] <name | id | ALL>
set cord va [alarmhi | alarmlo | warnhi | warnlo] <name | id | ALL> <value>
set cord va hyst <value>
set cord watts [alarmhi | alarmlo | warnhi | warnlo] <name | id | ALL> <value>
set cord watts hyst <value>
Parameters
The set cord command uses the following parameters:
Sub-Parameters
The set cord command uses the following sub-parameters:
Usage Guidelines
min <=alarmlo <=warnlo <=warnhi <=alarmhi <=max
Command Access
Admin level only
Using the Command Line Interface (CLI)
email
Email notifications for cord events.
hyst
Hysteresis between event state and recovery.
Maximum current load for a cord. 1-max factory current in show cords
loadmax
command.
name
Name for the cord. 0-32 characters.
nomvolts
Nominal voltage for the cord. 0-max factory voltage in show cords
command.
outofbal
Out-of-balance; the percent power difference between phases of a cord.
min 0%, max 200%, hyst 0-10% (default 2%).
pf
Power factor. min 0.00, max 1.00, hyst 0.0-0.20 (default 0.02).
snmpt
SNMP trap notifications for cord events.
va
Power (with power factor included). min 0VA, max (power capacity) in
cstat command, hyst 0-1000VA (default 100VA).
watts
Power (without power factor included). Min 0W, max (power capacity) in
cstat command, hyst 0-1000W (default 100W).
alarmhi
High alarm value.
alarmlo
Low alarm value.
warnhi
High warning alarm.
warnlo
Low warning alarm.
Switched PRO2 – User Guide