Parker 514C-04 Technical Manual page 15

Dc controller 514c series
Hide thumbs Also See for 514C-04:
Table of Contents

Advertisement

TERMINAL
FUNCTION
T18
Current Demand
Input / Output
T19
Health Output
T20
Enable Input
T21
Inverted Setpoint
Sum Output
T22
Thermistor /
Microtherm Input
T23
Zero Speed Output
/Zero Setpoint
Output
T24
+24V
The +24v supply from the drive (terminal T24) is for use with the drive only. It
should be used with the RUN circuit (terminal 5) to control the drives internal
relay to switch the contactor and can be used with the ENABLE circuit (terminal
T20).
C
a
u
t i o
n
CAUTION
DO NOT use the +24v supply to power any circuit or device external to the
drive. This includes external relays, PLC's, and any other equipment.
Using the +24v external to the drive could result in drive malfunction or damage,
damage to connected equipment, and could endanger personnel.
514C Product Manual
This manual was downloaded on www.sdsdrives.com
+44 (0)117 938 1800 - info@sdsdrives.com
DESCRIPTION
Analogue Input or Output:
SW1/8 'ON' = Current Demand
Output.
SW1/8 'OFF' = Current Demand Input.
0 to 7.5V = 0 to 150% Current.
Digital Output,
+24V = Healthy.
Digital Input to Enable Controller.
+10V to +24V to Enable.
0V to Disable.
Analogue Output,
0 to -10V = 0 to 100% Forward Speed.
Motor Thermistor or Microtherm Sensor
<200 ohm to 0V = Normal.
>1800 ohm to 0V= Overtemperature.
Digital Output,
+24V = Stopped/Zero Setpoint.
0V = Running/Non zero setpoint.
+24V Supply Output.
Pre-Installation Planning
5mA output
S/C protected approx.
100 kohm.
50mA Source
Short Circuit Protected.
100k approx.
5mA output
S/C protected.
5k approx.
50mA Source
Short Circuit Protected.
20mA. For use on the
drive only.
2-3
NOTES

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

514c-08514c-16514c-32514c

Table of Contents