Timer Reset Panel, Cabin Panel, Motion Detector, Flash Bea-
con
The wiring procedure is common to all the above-mentioned units.
Cable to use
Cable MPYC-7 (be-
tween respective unit
and BR-520)
1) Loosen four screws
to remove rear cover.
4.7.5

Flash Beacon

The LED of the Flash Beacon can be adjusted externally. Connect a junction box (lo-
cal supply) and external dimmer (3 kΩ, local supply) as shown below to enable the
adjustment.
DIMMER
To use an external dimmer, set the jumper block J2 to the 1-2 position.
Timer Reset Panel Max. length of single cable: 40 m Max. length: of all ca-
bles: 150 m Cabin Panel
Max. length of single cable: 80 m Max. length of all cables: 300 m
Cable total length Cabin Panel: max. 300 m Timer Reset Panel: max. 150
m
2) Process cable and connect cable
to WAGO terminal block.
Use terminal opener (inside
Processor Unit) to open terminals.
(Shown: Timer Reset Panel)
JUNCTION
BOX
Description
3) Close rear cover. Fasten
cable to clamp with cable
tie (supplied).
J2
FLASH
BEACON
4. INSTALLATION
4-15