6 Wiring
L
Power supply
1
AC 85 to 264V 50/60Hz
L
ARS
or
DC 20 to 62V
N
2
AC 20 to 55V
G
ARS
G
3
N
ARS
Port_B +
+
4
Non IS HART to NRF
-
or others port_B -
5
+
Digital output
6
RS485,V1 serial pulse
-
7
or remote HART
8
Alarm contact
9
A
Alarm Contact
B
NOTICE
・ Terminal connection for Whessoe Matic 550 (WM550) and Mark Space, refer to the next few pages.
・ Terminals 4 & 5 and 24 & 25 for HART devices are inter - connected on Explosion proof (Ex d) certified version.
・ Terminals 24 & 25 (and 24, 25 & 26 for spot temp.) will be intrinsically safe (i.s.) device connection
only when intrinsically safe certified version is selected.
Figure 39: Wiring sample 1
44
6.2
Terminal assignment
6.2.1
V1 Serial Signal, Modbus RS485, HART, Enraf BPM
10
Alarm contact
11
12
Alarm contact
13
14
Alarm contact
15
COM
16
HOIST (CTR1)
17
HOIST (CTR2)
18
19
+
20
4 to 20mA
Channel 1
-
21
+
4 to 20mA
22
Channel 2
-
23
+
Port_A +
24
A
local HART
-
25
B
port_A -
(see NOTICE.)
26
b
Operation
Ex d local (slave) HART
contact
Terminal No.: 4 and 5
input
NRF and other HART communication devices
NOTICE
Power supply
A
Ex d local (slave) HART
Terminals: 4 &5
C
B
Digital output: Terminals 6 & 7
V1 Serial Pulse, Modbus (RS485)
HART, Enraf BPM
Ex ia local (slave) HART, or
Pt100 3 wire spot RTD (see NOTICE.)
C
terminals: 24 & 25
4 to 20mA output:
Terminals 20 & 21, 22 & 23
CAUTION
Terminals 22 & 23 will be used as "Status 1 Input"
D
D
when signal input from field unit
(Order code position 60) is: Order information: 060
4: HART and Status 1 input
5: HART, Pt100 Spot and Status 1 input
6: HART, Pt100 Spot temp.,
Operation contact, and Status 1 input
Proservo NMS5
A
B
b
Cable entry descriptions
Endress+Hauser
Need help?
Do you have a question about the Proservo NMS5 and is the answer not in the manual?