Proservo NMS5
GVH846 LIQ. WAIT TIME
Item
Matrix Group : TANK PROFILE
Function
Group
GVH846
LIQ. WAIT
TANK
PROFILE
TIME
Figure 72: GVH846
GVH847 OPE. WAIT TIME
Item
Matrix Group : TANK PROFILE
Function
Group
TANK
PROFILE
Figure 73: GVH847
Endress+Hauser
1. Select GVH846 "LIQ. WAIT TIME" to deter-
mine the displacer weight calibration interval
between each measuring point in the liquid.
2. Enter desired waiting time by pressing + or -
key, and select E to enter.
1. Select GVH847 "OPE. WAIT TIME".
2. Enter desired waiting time by pressing + or -
key, and select E to enter.
GVH847
OPE. WAIT
TIME
Procedure
Procedure
8 Commissioning
Remarks
• Set access code to 51. A small turbulence
made by the movement of displacer itself
may cause the liquid surrounding displacer
to be unstable for the accurate
measurement.
• This function allows displacer to hold in
each calculated position before actual
measurement is proceeded based on the
entered value.
Remarks
• Set access code to 51.
• This function determines how long for the
NMS to wait if "BAL. LEVEL" can not be
established before quitting entire operation.
79