5.2.3 Setting Basic Application Parameters

After running the Oriented Start-up routine and properly setting the parameters, the inverter is ready to operate
in the V/f mode.
The inverter has a number of other parameters that allow its adaptation to the most different applications.
This manual presents some basic parameters that shall be set in most cases. There is a group named "Basic
Application" to make this task easier. A summary of the parameters inside this group is listed in table 5.1. There
is also a group of read only parameters that shows the value of the most important inverter variables such as
voltage, current, etc. The main parameters comprised in this group are listed in table 5.2. For further details,
please refer to the CFW-11 Software Manual.
Follow steps outlined in figure 5.3 to set the parameters of the Basic Application group.
The procedure for start-up in the V/f operation mode is finished after setting these parameters.
Step
Action/Result
- Monitoring Mode.
1
- Press "Menu"
(right soft key).
- Group "00
ALL PARAMETERS" has
2
been already selected.
- Group "01
PARAMETER GROUPS" is
3
then selected.
- Group "02
ORIENTED START-UP" is
4
then selected.
- Group "03
CHANGED
PARAMETERS" is
5
selected.
Display indication
Ready
0rpm
LOC
0
rpm
0.0
A
0.0
Hz
15:45
Menu
Ready
LOC
0rpm
00 ALL PARAMETERS
01 PARAMETER GROUPS
02 ORIENTED START-UP
03 CHANGED PARAMETERS
Return
15:45
Select
Ready
0rpm
LOC
00 ALL PARAMETERS
01 PARAMETER GROUPS
02 ORIENTED START-UP
03 CHANGED PARAMETERS
Return
15:45
Select
Ready
LOC
0rpm
00 ALL PARAMETERS
01 PARAMETER GROUPS
02 ORIENTED START-UP
03 CHANGED PARAMETERS
Return
15:45
Select
Ready
0rpm
LOC
00 ALL PARAMETERS
01 PARAMETER GROUPS
02 ORIENTED START-UP
03 CHANGED PARAMETERS
Return
15:45
Select
Figure 5.3 - Setting parameters of the Basic Application group
First Time Power-Up and Start-Up
Step
Action/Result
- Group "04 BASIC
APPLICATION" is
6
selected.
- Press "Select".
- Parameter "Acceleration
Time P0100: 20.0 s" has
been already selected.
- If needed, set P0100
according to the desired
acceleration time. To do
7
so, press "Select".
- Proceed similarly until all
parameters of group "04
BASIC APPLICATION"
have been set. When
finished, press "Return"
(left soft key).
8
- Press "Return".
- The display returns to the
9
Monitoring Mode and the
inverter is ready to run.
Display indication
Ready
0rpm
LOC
01 PARAMETER GROUPS
02 ORIENTED START-UP
03 CHANGED PARAMETERS
04 BASIC APPLICATION
Return
15:45
Select
Ready
0rpm
LOC
Acceleration Time
P0100:
20.0s
Deceleration Time
P0101:
20.0s
Return
15:45
Select
Ready
0rpm
LOC
01 PARAMETER GROUPS
02 ORIENTED START-UP
03 CHANGED PARAMETERS
04 BASIC APPLICATION
Return
15:45
Select
Ready
0rpm
LOC
0
rpm
0.0
A
0.0
Hz
15:45
Menu
5-5
5