Installation and Connection
ATTENTION!
When arranging two or more inverters vertically, respect the minimum clearance A + B (figure 3.2)
and provide an air deflecting plate so that the heat rising up from the bottom inverter does not affect
the top inverter.
ATTENTION!
Provide conduit for physical separation of the signal, control, and power conductors (refer to item
3.2 - Electrical Installation).
3
Air flow
(a) Surface Mounting
3-2
335 (13.2)
200 (7.8)
∅ c2
c2
c3
Model
M
M
Frame E
M8
M8
Tolerances for dimensions d3 and e3: +1.0 mm (+0.039 in)
Tolerances for remaining dimensions: ±1.0 mm (±0.039 in)
(*) Recommended torque for the inverter mounting (valid for c2 and c3)
Figure 3.1 (a) and (b) - Mechanical installation details - mm (in)
358 (14.1)
168 (6.6)
Air flow
Max. 3 (0.12)
(b) Flange Mounting
d3
e3
Torque (*)
mm
mm
N.m
(in)
(in)
(lbf.in)
315
615
20.0
(12.40)
(24.21)
(177.0)
275 (10.8)
d3
∅ c3