KEYPAD AND DISPLAY
This chapter describes:
- The operator keys and their functions;
- The indications on the display;
- How parameters are organized.

4.1 INTEGRAL KEYPAD - HMI-CFW11

The integral keypad can be used to operate and program (view / edit all parameters) of the CFW-11 inverter.
The inverter keypad navigation is similar to the one used in cell phones and the parameters can be accessed
in numerical order or through groups (Menu).
Left soft key: press this key to select the
above highlighted menu feature.
1. Press this key to advance to the next pa-
rameter or to increase a parameter value.
2. Press this key to increase the speed.
3. Press this key to select the previous
group in the Parameter Groups.
Press this key to define the direction of
rotation for the motor.
This option is active when:
P0223=2 or 3 in LOC and/or
P0226=2 or 3 in REM
Press this key to switch between LOCAL
or REMOTE modes.
This option is active when:
P0220=2 or 3
Battery:
NOTE!
The battery is necessary only to keep the internal clock operation when the inverter stays without
power. If the battery is completely discharged or if it is not installed in the keypad, the displayed clock
time will be invalid and an alarm condition 'A181 - Invalid clock time' will be indicated whenever the
AC power is applied to the inverter.
The battery life expectancy is of approximately 10 years. When necessary, replace the battery by another of the
CR2032 type.
Press this key to accelerate the motor to the speed set in
P0122 in the time set for the acceleration ramp.
The motor speed is kept while this key is pressed.
Once this key is released, the motor will stop by following the
deceleration ramp.
This function is active when all conditions below are satisfied:
1. Start/Stop=Stop;
2. General Enable=Active;
3. P0225=1 in LOC and/or P0228=1 in REM.
Figure 4.1 - Operator keys
Keypad and Display
Right soft key: press this key to select
the above highlighted menu feature.
1. Press this key to move back to the previous
parameter or to decrease a parameter value.
2. Press this key to decrease speed.
3. Press this key to select the next group in
the Parameter Groups.
Press this key to accelerate the motor in the
time set for the acceleration ramp.
This option is active when:
P0224=0 in LOC or
P0227=0 in REM
Press this key to stop the motor in the time set
for the deceleration ramp.
This option is active when:
P0224=0 in LOC or
P0227=0 in REM