Control Connections - WEG CFW-11 User Manual

Hide thumbs Also See for CFW-11:
Table of Contents

Advertisement

Installation and Connection

3.2.5 Control Connections

The control connections (analog inputs/outputs, digital inputs/outputs), shall be performed in connector XC1
of the CC11 control board.
Functions and typical connections are presented in figures 3.18 (a) and (b).
CW
≥5kΩ
CCW
rpm
3
amp
3-22
Connector XC1
Factory Default Function
Positive reference for
1
+REF
potentiometer
Analog input #1:
2
AI1+
Speed reference (remote)
3
AI1-
Negative reference for
4
REF-
potentiometer
Analog input #2:
5
AI2+
No function
6
AI2-
Analog output #1:
Speed
7
AO1
Reference (0 V) for the analog
AGND
8
outputs
(24 V)
Analog output #2:
Motor current
9
AO2
Reference (0 V) for the analog
AGND
10
outputs
(24 V)
Reference (0 V) for the 24 Vdc
11
DGND *
power supply
Common point of the digital
12
COM
inputs
24 Vdc power supply
13
24 Vdc
Common point of the digital
14
COM
inputs
Digital input #1:
15
DI1
Start / Stop
Digital input #2:
16
DI2
Direction of rotation (remote)
Digital input #3:
17
DI3
No function
Digital input #4:
18
DI4
No function
Digital input #5:
19
DI5
Jog (remote)
Digital input #6:
20
DI6
2
ramp
nf
Digital output #1 DO1 (RL1):
21
NC1
No fault
22
C1
23
NO1
Digital output #2 DO2 (RL2):
24
NC2
N > N
- Speed > P0288
25
C2
X
26
NO2
Digital output #3 DO3 (RL3):
27
NC3
N* > N
- Speed reference >
28
C3
X
P0288
29
NO3
Figure 3.18 (a) - Signals at connector XC1 - Digital inputs working as 'Active High'
Specifications
Output voltage:+5.4 V, ±5 %.
Maximum output current: 2 mA
Differential
Resolution: 12 bits
Signal: 0 to 10 V (R
=400 kΩ) / 0 to 20 mA / 4 to 20 mA (R
IN
Maximum voltage: ±30 V
Output voltage: -4.7 V, ±5 %.
Maximum output current: 2 mA
Differential
Resolution: 11 bits + signal
Signal: 0 to ±10 V (R
=400 kΩ) / 0 to 20 mA / 4 to 20 mA (R
IN
Maximum voltage: ±30 V
Galvanic Isolation
Resolution: 11 bits
Signal: 0 to 10 V (R
≥ 10 kΩ) / 0 to 20 mA / 4 to 20 mA (R
L
Protected against short-circuit.
Connected to the ground (frame) through impedance: 940 Ω resistor in
parallel with a 22 nF capacitor.
Galvanic Isolation
Resolution: 11 bits
Signal: 0 to 10 V (R
≥ 10 kΩ) / 0 to 20 mA / 4 to 20 mA (R
L
Protected against short-circuit.
Connected to the ground (frame) through impedance: 940 Ω resistor in
parallel with a 22 nF capacitor.
Connected to the ground (frame) through impedance: 940 Ω resistor in
parallel with a 22 nF capacitor.
24 Vdc power supply, ±8 %.
Capacity: 500 mA.
Note: In the models with the 24 Vdc external control power supply
(CFW11XXXXXXOW) the terminal 13 of XC1 becomes an input, i.e., the
user must connect a 24 V power supply for the inverter (refer to the section
7.1.4 for more details). In all the other models this terminal is an output,
i.e., the user has a 24 Vdc power supply available there.
6 isolated digital inputs
High level ≥ 18 V
Low level ≤ 3 V
Maximum input voltage = 30 V
Input current: 11 mA @ 24 Vdc
Contact rating:
Maximum voltage: 240 Vac
Maximum current: 1 A
NC - Normally closed contact;
C - Common;
NO - Normally open contact.
=500 Ω)
IN
=500 Ω)
IN
≤ 500 Ω)
L
≤ 500 Ω)
L

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents