Connecting-up
5.2 Connecting the line and motor cable at the inverter
When using the inverter in the first environment, also carefully observe the information in
Section
Table 5- 1
Frame
size
FSA
FSB
FSC
FSD
FSE
FSF
FSGX
External filter:
1)
44
Inverter applications (Page 75)
Permissible length of motor connecting cables
Inverter with filter, category
C2, internal or external
EMC category
First/sec
Second
ond
envi-
envi-
ronment,
ronment,
C3
C2
Shielded Shielded Shield-
25 m
25 m
25 m
25 m
25 m
25 m
25 m
25 m
25 m
25 m
25 m
25 m
25 m
25 m
Line filter (Page 88)
1)
No
Without output
EMC
reactor/
catego-
without sine-
ry
wave filter
Shield-
Un-
ed
ed
shield-
ed
50 m
50 m
100 m
50 m
50 m
100 m
50 m
50 m
100 m
50 m
50 m
100 m
50 m
50 m
100 m
50 m
50 m
100 m
200 m
200 m
300 m
Hardware Installation Manual, 07/2016, A5E36985441C AA
Inverter without filter
No EMC category
With output reactor
With sine-wave
Shielded
Un-
Shielded
shielded
100 m
100 m
200 m
100 m
150 m
200 m
100 m
150 m
200 m
200 m
300 m
200 m
200 m
300 m
200 m
200 m
300 m
200 m
300 m
450 m
300 m
Power Modules PM240
filter