Connecting-up
5.1 Permissible line supplies
5.1.4

Protective conductor

Danger to life caused by high leakage currents for an interrupted protective conductor
The drive components conduct a high leakage current via the protective conductor.
Touching conductive parts when the protective conductor is interrupted can result in death
or serious injury.
• Dimension the protective conductor as stipulated in the appropriate regulations.
Dimensioning the protective conductor
Observe the local regulations for protective conductors subject to an increased leakage
current at the site of operation.
The minimum cross-section of the protective conductor
section of the line or motor feeder cable:
● Line or motor feeder cable ≤ 16 mm
⇒ Minimum cross-section of the protective conductor = cross-section of the line or motor
feeder cable
● 16 mm² < line or motor feeder cable ≤ 35 mm
⇒ Minimum cross-section of the protective conductor = 16 mm
● Line or motor feeder cable > 35 mm
⇒ Minimum cross-section of the protective conductor = ½ cross-section of the line or
motor feeder cable
40
WARNING
Protective conductor for line feeder cables
Protective conductor for inverter line feeder cables
Protective conductor between PE and the electrical cabinet
Protective conductor for motor feeder cables
...
2
2
2
Hardware Installation Manual, 07/2016, A5E36985441C AA
depends on the cross-
2
Power Modules PM240

Hide quick links: