50/60 Hz Toggling; Number Of Support Points; Load Cell Characteristic Value; Rated Load Of A Load Cell - Siemens SIWAREX WP321 Manual

Electronic weighing system
Hide thumbs Also See for SIWAREX WP321:
Table of Contents

Advertisement

Scale parameters and functions
8.9 DR 10 load cell parameters
8.9.1

50/60 Hz toggling

To improve the suppression of faults caused by the supply network, you can specify the
network frequency for signal filtering. The measuring rate is 100 Hz for the 50 Hz setting,
and 120 Hz for the 60 Hz setting.
8.9.2

Number of support points

If no anchor points are used, the number of support points is equal to the number of load
cells.
If anchor points are used in addition to load cells, the number of support points is equal to
the total number of load cells and fixed support points.
8.9.3

Load cell characteristic value

The load cell characteristic value is required to correctly interpret the output voltage from the
load cell. This specification is also necessary for determining load cell overload. The exact
value can be entered if the measurement log for the load cell is available. The mean value
can be entered if there is more than one load cell.
Example
Characteristic value = 2.018 mV/V
8.9.4

Rated load of a load cell

The rated load of a load cell is required for checking the maximum weighing range of the
scales. The rated load is entered in the specified units of weight.
68
SIWAREX WP321
Manual, 07/2014, A5E33715669A-02

Advertisement

Table of Contents
loading

Table of Contents