2. Apply the Master's Explicit Request Messages to set the Identify object.
Device Heartbeat interval Attribute ID : 0x0A
Master (MAC ID =0x0A)
_ Group 2 Message
|
_ Destination MAC ID=0x09
|
|
_ Message ID =4
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ID=10 001001 100. Data= 0A 10 01 01
Slave response Device Heartbeat Message every two seconds.
_ Group 2 Message
|
_ Source MAC ID=0x09
|
|
_ Message ID =3
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ID=10 001001 011. Data=0A CD 01 00 03 00 00 00
If users want to cancel the heartbeat message, they must set the heartbeat
interval attribute value of the Identity object instance to zero.
I-7242D DeviceNet/Modbus RTU Gateway User's Manual, July 2006, Version 1.1
_ Frag=0. Transaction ID=0. Source MAC ID= 0x0A
|
_ Service=set attribute
|
| _ Class ID=1
|
| | _ Instance ID=1
|
| | | _
Attribute ID= 0x0A
|
| | | |
_
Attribute Data= 2 seconds
0A 02 00
_ Frag=0. Destination MAC ID= 0x09
|
_ Service code=0x4D
|
|
_ Identity Object Instance ID=1
|
|
|
_ Device State=3
|
| __|_ _|__ ____ EV, SF, UF, DF and Consistency value