3. Apply the Master's Explicit Request Messages to set the User-defined
Modbus command object instance attribute 0x03.
Set the response Modbus message length = 0x07 bytes
Master (MAC ID =0x0A)
_ Group 2 Message
|
_ Destination MAC ID=0x09
|
|
_ Message ID =4
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ID=10 001001 100. Data= 0A 10 65 01 03
_ Group 2 Message
|
_ Source MAC ID=0x09
|
|
_ Message ID =3
|
|
|
|
|
|
|
|
|
|
|
|
ID=10 000011 011. Data= 0A 90
I-7242D DeviceNet/Modbus RTU Gateway User's Manual, July 2006, Version 1.1
_ Frag=0. Transaction ID=0. Destination MAC ID= 0x0A
|
_ Service=Set Attribute Request
|
| _ Class ID=0x65
|
| | _ Instance ID=0x01
|
| | | _ Attribute ID=0x03
|
| | | |
_
Attribute Data= 0x07 – Response Modbus Command
07
_ Frag=0. Transaction ID=0. Destination MAC ID= 0x0A
|
_ Service= Set Attribute Response
|
|
|
|