5 SETTINGS
Hardware and software is provided to receive signals from external transducers and convert these signals into a digital
format for use as required. The relay will accept inputs in the range of –1 to +20 mA DC, suitable for use with the most
common transducer output ranges; all inputs are assumed to be linear over the complete range.
The Input Range setting specifies the mA DC range of the transducer connected to the input channel.
Range : -1 to 0, 0 to 1, -1 to 1, 0 to 5, 0 to 10, 0 to 20, 4 to 20.
The Min and Max Value settings are used to program the span of the transducer in primary units.
Min Value : -9999.99 to 9999.99
Max Value : -9999.99 to 9999.99
GEK-113032A
W650 Wind Generator Protection System
5.6 INPUTS/OUTPUTS

5.6.6 ANALOG BOARDS SPECIFIC SETTINGS