4.1 ENERVISTA 650 SETUP SOFTWARE INTERFACE
Table 4–18: ACTUAL VALUES INCLUDED IN THE PROTECTION MENU
PROTECTION
4
Table 4–19: ACTUAL VALUES RELATED TO RECORDING FUNCTIONS IN THE RECORDS STATUS MENU:
RECORD
STATUS
4-28
Protection Blocks
This screen shows all the protection element blocks available. Protection
elements block signals can be configured at "Setpoint>Relay
Configuration > Protection Elements".
Phase Current
Protection status signals (pickups and operations) for time overcurrent,
instantaneous overcurrent and directional protection functions for phase
current.
Neutral Current
Protection status signals (pickups and operations) for time overcurrent,
instantaneous overcurrent and directional protection functions for neutral
current (calculated from phases).
Ground Current
Protection status signals (pickups and operations) for time overcurrent,
instantaneous overcurrent and directional protection functions for ground
current (measured from 4
Sensitive Ground
Protection status signals (pickups and operations) for time overcurrent,
Current
instantaneous overcurrent, isolated and directional protection functions
for ground current (measured from 5
Negative Sequence
Protection status signals (pickups and operations) for negative sequence
Current
time overcurrent function.
Voltage
Protection status signals (pickups and operations) for all voltage
functions, undervoltage, overvoltage, neutral overvoltage, and auxiliary
under and over voltage.
Power
Protection status signals (pickups and operations) for directional power
units.
Fault Reports
This menu shows the fault report status signals, as fault report trigger,
fault date, fault type and location, besides the fault report number.
Control Events
Status of the control events (if the signal configured to launch the control
event is active or not).
Oscillography
Status of signals related to oscillography recording, such as status or
digital channels, oscillography trigger, number of records available, etc.
Data Logger
Data logger information about oldest and newest sample time stamp,
and number of channels and days configured in data logger settings.
Demand
Demand trigger and reset inputs status.
Energy
Freeze, unfreeze and reset input signals for energy counters.
Breaker Maintenance
All signals related to breaker maintenance, such as number of openings,
closings, (KI)
W650 Wind Generator Protection System
th
current input).
th
current input).
2
2
t counters, alarm signal for (KI)
4 HUMAN INTERFACES.
t, etc.
GEK-113032A