GE Multilin W650 Instruction Manual page 611

Wind generator protection system instruction manual gek-113032a
Table of Contents

Advertisement

APPENDIX E
SETPOINT > INPUTS/OUTPUTS > CONTACT I/O >
BOARD F > BOARD G
SETTING DESCRIPTION
I/O board type (available only for CIO
modules)
Input activation voltage threshold
Group A
Input activation voltage threshold
Group B
Debounce time for Group A
Debounce time for Group B
Input type
Input signal time delay
Output logic type
Output type
Output pulse length
Snapshot event generation
NOTE 2: DESCRIPTION OF X, Y AND Z IN INPUT/OUTPUT BOARDS
X
For the I/O board selection in the relay
model:
CCY
0Z
GEK-113032A
NAME
DEFAULT VALUE
I/O Board Type_H
NONE
Voltage Threshold
80
A_X
Voltage Threshold
80
B_X
Debounce Time A_X
15
Debounce Time B_X
15
Input Type_X_CCY
POSITIVE
(CCY)
Delay Input
0
Time_X_CCY (CCY)
Output Logic_X_0Z
POSITIVE
Output Type_X_0Z
NORMAL
Pulse Output
10000
Time_X_0Z
Snapshot Events
ENABLED
F or G, , the I/O board name, depending on the Relay model.
F and G are internal Relay boards.
I/O BOARD TYPE
ENERVISTA 650
ASSOCIATED DIGIT
SETUP BOARD
SETTINGS
0
NONE
1
16 INP+ 8 OUT
8 INP +8 OUT
2
+SUPV
4
32 INP
5
16 INP + 8 ANA
Is the name used for inputs in I/O boards
Mixed, 16 digital inputs: CC1....CC16
Supervision: 8 digital inputs: CC1,..., CC8
32 INP: 32 digital inputs; CC1,...,CC32
Is the name used for the different outputs in I/O boards, 8 outputs available for any of the two
types of board (01,...., 08)
W650 Wind Generator Protection System
E.1 FACTORY DEFAULT SETTINGS
STEP
RANGE
[NONE,
N/A
16 INP + 8OUT,
8 INP + 8OUT + SUPV]
1 V
[20 : 230]
1 V
[20 : 230]
1 ms
[1 : 50]
1 ms
[1 : 50]
[POSITIVE-EDGE,
NEGATIVE-EDGE,
N/A
POSITIVE,
NEGATIVE]
1 ms
[0 : 60000]
[POSITIVE,
N/A
NEGATIVE]
[NORMAL,
N/A
PULSE,
LATCH]
1 ms
[0 : 60000]
N/A
[DISABLED – ENABLED]
BOARD TYPE
None
Mixed
Supervision
32 digital inputs
16 digital inputs + 8 analog inputs
USER
VALUE
E