GE Multilin W650 Instruction Manual page 547

Wind generator protection system instruction manual gek-113032a
Table of Contents

Advertisement

APPENDIX B
ADDRESS BIT
NAME
Ajustes Demanda - Demand
0x2F0B
Trigger Enabled
0x2F0C
Snapshot Events
0x2F1F
Confirmation address
Ajustes Protocolo IEC 870-5-104
0x2F20
Function
0x2F21
TCP Port
0x2F23
Common Addr of ASDU
0x2F25
Cyclic Meter Period
0x2F27
Synchronization Event
0x2F5A
Confirmation address
Ajustes Sobreintensidad Temporizada de Fases Nivel Alto Grupo 1 - Phase TOC Low 1
0x32A5
Function
0x32A6
Input
0x32A7
Pickup Level
0x32A9
Curve
0x32AA
TD Multiplier
0x32AC
Reset
0x32AD
Voltage Restraint
0x32AE
Snapshot Events
0x32C1
Confirmation address
GEK-113032A
FORMAT STEP MODE LENGTH MISCELLANEOUS
F012
1
R/W
F012
1
R/W
W
F012
1
R/W
F005
1
R/W
F005
1
R/W
F005
1
R/W
F005
1
R/W
W
F012
1
R/W
F012
1
R/W
F003
1
R/W
F012
1
R/W
F003
1
R/W
F012
1
R/W
F012
1
R/W
F012
1
R/W
W
W650 Wind Generator Protection System
B.7 MEMORY MAP
1
0=DISABLED
1=ENABLED
1
0=DISABLED
1=ENABLED
1
1
0=DISABLED
1=ENABLED
2
[0 , 65535]
2
[0 , 65535]
2
[0 , 3600]
2
[0 , 3600]
1
1
0=DISABLED
1=ENABLED
1
0=PHASOR(DFT)
1=RMS
2
[0.05 , 160.00] A
1
0=IEEE Ext Inv
1=IEEE Very Inv
2=IEEE Mod Inv
3=IEC Curve A
4=IEC Curve B
5=IEC Curve C
6=IEC Long-Time Inv
7=IEC Short-Time Inv
8=IAC Ext Inv
9=IAC Very Inv
10=IAC Mod Inv
11=ANSI Ext Inv
12=ANSI Very Inv
13=ANSI Norm Inv
14=ANSI Mod Inv
15=I2t
16=Definite Time
17=Rectifier Curve
18=User Curve A
19=User Curve B
20=User Curve C
21=User Curve D
2
[0.00 , 900.00] s
1
0=INSTANTANEOUS
1=LINEAL
1
0=DISABLED
1=ENABLED
1
0=DISABLED
1=ENABLED
1
B
B-101

Advertisement

Table of Contents
loading

Table of Contents