3.3 MECHANICAL DESCRIPTION

3.3MECHANICAL DESCRIPTION
The model number and electrical characteristics of the unit are indicated on the label located on the right side of the relay
case.
The metallic case of the unit is highly resistant to corrosion. It is made of stainless steel (AISI 304), coated with an epoxy
layer, and the rest of the metallic pieces are covered with a high quality resistive coating that has successfully passed at
least 96 hours in the salt spray chamber (S/N ASTM B-117).
The front of the relay is made of a conductor thermoplastic, flame retardant (V0), highly resistive material, which
guarantees the unit's immunity to all kinds of EMI/RFI/ESD interferences. As well, an IP51 (IEC 529) protection degree
against dust and water through the front and with the relay mounted in the panel.
In order to guarantee safety and preventing access to the unit by unauthorized personnel, the front part of the relay has a
sealable cover to protect the RS 232 front port and the operation mode key.
3

3.3.1 MOUNTING

The unit is designed for semi-flush mounting. The relay is secured to the panel with the 4 M6 screws provided with the unit.
The user has access to the front keypad, display and communication port. The wiring is at the rear of the unit. The drilling
dimensions are shown on Figure 3–4:.
Figure 3–3: PANEL MOUNTING
The relay width allows the mounting of two units on a standard 19'' panel, 6 units high.