5.4 PROTECTION ELEMENTS
5.4.8.3 NEUTRAL OVERVOLTAGE ELEMENT (HIGH LEVEL AND LOW LEVEL) (59NH/59NL)
The Neutral Overvoltage element can be used to detect an asymmetrical system voltage condition due to a ground fault or
to the loss of one or two phases of the source.
The element responds to the system neutral voltage (3V0), calculated from the phase voltages or measured by the 4th
voltage transformer.
VT errors and normal voltage unbalance must be considered when setting this element.
The element time delay is selectable between 0 and 900 seconds and incorporates a reset with a selectable delay between
0 and 900 seconds.
Notice that the neutral overvoltage element will not be available if a DELTA Connection is set in the Phase VT Connection
setting in General settings, and the fourth voltage transformer input is set to the busbar voltage (Vx in Auxiliary Voltage
setting). This is because with this combination of settings it is not possible to calculate the zero sequence component from
the phase-to-phase voltage magnitudes.
Table 5–63: 59NH/59NL ELEMENT SETTINGS
SETPOINT > PROTECTION ELEMENTS > VOLTAGE ELEMENTS >
>NEUTRAL OV HIGH > NEUTRAL OV HIGH 1> NEUTRAL OV HIGH 2 > NEUTRAL OV HIGH 3
>NEUTRAL OV LOW > NEUTRAL OV LOW 1> NEUTRAL OV LOW 2 > NEUTRAL OV LOW 3
SETTING DESCRIPTION
Function permission
Pickup Level
Trip time
Reset time
5
Snapshot Event generation
The snapshot event setting enables or disables the snapshot event generation for this element.
5.4.8.4 AUXILIARY OVERVOLTAGE ELEMENT (59X)
This is an Auxiliary overvoltage element for general use that uses as its input magnitude the voltage measured by the 4
VT. The time delay for element 59X can be set from 0 to 900 seconds. The element has a reset than can be programmed
from 0 to 900 seconds.
Table 5–64: 59X ELEMENT SETTINGS
SETPOINT > PROTECTION ELEMENTS > VOLTAGE ELEMENTS > AUXILIARY OV >
AUXILIARY OV 1> AUXILIARY OV 2 > AUXILIARY OV 3
SETTING DESCRIPTION
Function permission
Pickup Level
Trip time
Reset time
Snapshot Event generation
The snapshot event setting enables or disables the snapshot event generation for this element.
5-66
NAME
DEFAULT VALUE STEP
Function
DISABLED
Pickup Level
50
Trip Delay
10.00
Reset Delay
0.00
Snapshot Events
ENABLED
NAME
DEFAULT VALUE
Function
DISABLED
Pickup Level
50
Trip Delay
10.00
Reset Delay
0.00
Snapshot Events
ENABLED
W650 Wind Generator Protection System
RANGE
N/A
[DISABLED – ENABLED]
1 V
[3 : 500 ]
0.01 s
[0.00 : 900.00]
0.01 s
[0.00 : 900.00]
N/A
[DISABLED – ENABLED]
STEP
RANGE
N/A
[DISABLED – ENABLED]
1 V
[3 : 500]
0.01 s
[0.00 : 900.00]
0.01 s
[0.00 : 900.00]
N/A
[DISABLED – ENABLED]
5 SETTINGS
th
GEK-113032A