5.8 RELAY CONFIGURATION
5.8.3.1 HOW TO PROGRAM AN OPERATION
Example of how to program an operation to close a breaker with an operating time of 90 ms (closing), incorporating 52/b
contacts to indicate the change of position, using an interlock logic to enable the operation if
PROGRESS
there is no autoreclose in progress. The operation must be commanded from the relay faceplate using one
of the available operation push buttons.
To configure the related operation, go to Setpoint > Relay Configuration and select Operations tab.
This screen shows all the fields required for the operations configuration in the W650. In order to select an operation, press
on the operation name under the Select column, and all the related parameters will be enabled. The chosen name for the
operation is entered in "Command Text". To configure an interlock logic, select the Logic option in "Interlocks Type".
Once this option has been selected, the interlock configuration screen will be enabled. To display this screen, click on
"Press for Logic" for the desired operation on its Interlocks column. On this Interlocks screen, the two conditions that
conform the Interlock that enables the operation have been selected. To save the interlock, press on the disk icon on the
toolbar. A "Logic Saved" message will be displayed.
Once the Interlocks have been defined, the user must define the success conditions for the operation, define Final State
Type as LOGIC, and a "PRESS FOR LOGIC" message will light up below Final States. When clicking on "PRESS FOR
LOGIC", the success condition screen will be displayed, defining there as BREAKER CLOSED.
The front key to be used for executing the Operation can be selected on the Frontal Key column, in this example the Key I
option is selected on "Frontal Key". As none of the other contact input or virtual output options are going to be used they
will be set as None. The success condition time "Time out" is set to 500 ms, and the operation is only enabled through the
relay keypad, so only the MMI option is selected, thus disabling the rest of options (COM1, COM2, ETHERNET master are
not selected).
All the selections previously related are summarized in the following table:
5
Table 5–86: OPERATION SETTINGS
OPERATION
Operation1
Finally, configure a contact output to be activated with the programmed Operation (Operation1).
5-112
COMMAND TEXT
SETTINGS
CLOSE BREAKER
INTERLOCK (LOGIC)
FINAL STATES (LOGIC)
FRONT KEY
INPUT
VIRTUAL OUTPUT
TIMEOUT
CHANNELS
W650 Wind Generator Protection System
5 SETTINGS
Not AR RLC IN
VALUE/SOURCE
Not AR RLC IN PROGRESS
BREAKER CLOSED
I Key
Not configured
Not configured
500
MMI
GEK-113032A