7.2 IEC 61850 PROFILE FOR W650
7.2.3.5 LOGICAL NODES FOR METERING AND MEASUREMENT. LN GROUP: M
a) MMXU (MEASUREMENT)
MMXU CLASS
Attribute
Attr.
Name
Type
MMXU
DATA
Common Logical Node Information
Mod
geModINC
Beh
geINS
Health
geINS
NamPlt
geLPL
Measured values
TotW
GeIntMV
TotVAr
GeIntMV
TotVA
GeIntMV
TotPF
GeIntMV
Hz
GeIntMV
PPV
geIntDEL
PhV
geIntPhsWYE
A
geIntWYE
7
7-28
Explanation
Measurement
Mode
Behaviour
Health
Name plate
Total active power (P)
Total reactive power (Q)
Total apparent power (S)
Average power factor (PF)
Frequency
Phase to phase voltages (VL1L2,...)
Phase to ground voltages (VL1ER, ...)
Phase currents (IL1, ...)
W650 Wind Generator Protection System
7 IEC 61850 PROTOCOL
M/O Notes
M
M
M
M
O
Phase Real Pwr
O
Ph Reactive Pwr
O
Ph Apparent Pwr
O
3 Ph Power Factor
O
Frequency
O
Vxx Primary
O
Vx Primary
O
Phasor Primary