Danfoss DHP-A Installation Manual page 29

Domestic heat pumps
Hide thumbs Also See for DHP-A:
Table of Contents

Advertisement

Installation Guide
The brine pipes must be insulated from the heat pump, through the walls and outside the house all the way to the collector so as to
avoid condensation and prevent heat loss.
If the brine pipes are to be routed above ground, drill holes in the walls for them.
If the brine pipes are to be routed below ground see the instructions below.
2
3
1. Drill holes in the wall for the insert pipes (1) for the brine pipes. Follow the dimension and connection diagrams. If there is any risk
of groundwater infiltration at brine pipe lead-ins, watertight grommets must be used.
2. Position the insert pipes (1) in the holes sloping downwards. The inclination must be at least 1cm every 30 cm. Cut them at an angle
(as illustrated) so that rain water cannot get into the pipes.
3. Insert the brine pipes (2) into the insert pipes in the installation room.
4. Fill in the holes around the lines with mortar (3).
5. Ensure that the brine pipes (2) are centred in the insert pipes (1) so that the insulation is distributed equally on all sides.
6. Seal the insert pipes (1) with a suitable sealant (foam) (4).
5.3.3
Install brine pipes
When the brine lines are connected to the right for DHP-A, the brine out line must be routed over the brine
Caution
pump, under the compressor's vacuum pipe and under the condenser's flexible hose, see figure below.
Caution
Applies to DHP-A:
Note that the outdoor unit may move during defrosts, use flexible hoses to connect the pipes from the heat
pump and pipes on the outdoor unit.
Danfoss Heating Solutions
Domestic heat pumps
3
4
1
1
VMGFQ102
1
Insert pipe
2
Brine pipe
3
Mortar
4
Sealant
29

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents