Interrupts/diagnostic alarms

13.3 Diagnostic alarms

13.2.2

Diagnostics interrupt

Diagnostic interrupt
The module generates a diagnostic error interrupt at the following events:
● Channel is temporarily unavailable
● Hardware interrupt lost
● Error
● Supply voltage missing
● Parameter assignment error
● Low limit voltage violated (measuring voltage < 80 V)
● High limit value voltage exceeded
● Underflow voltage (tolerance for supply voltage) violated
● Overflow voltage (tolerance for supply voltage) exceeded
● Overload (current measurement > 12 A or tolerance overcurrent exceeded after expiry of
the tolerance time)
● Overflow of the calculated values (measured or calculated values screen exceed the
representable range of values)
See also
Diagnostic alarms (Page 88)
13.3
Diagnostic alarms
Diagnostic alarms
Note
Assignment channel in diagnostic message ⇔ Phase
In the diagnostic messages the channels are counted from "Channel "0" on, in the AI Energy
Meter 480VAC ST from Phase "1" on.
Note the following assignment:
• Channel "0" ⇔ Phase "1"
• Channel "1" ⇔ Phase "2"
• Channel "2" ⇔ Phase "3"
88
Analog input module AI Energy Meter 480VAC ST (6ES7134-6PA20-0BD0)
Manual, 12/2015, A5E36061895-AA