Parameter data records
A.2 Structure of the parameter data record 128 for the entire module
Image A-6
Error while transferring the data record
The module always checks all the values of the transferred data record. Only if all the values
were transferred without errors does the module apply the values from the data record.
The WRREC instruction for writing data records returns corresponding error codes when
errors occur in the STATUS parameter.
The following table shows the module-specific error codes and their meaning for the
parameter data record 128.
Error code in STATUS parame-
ter
(hexadecimal)
Byte 0 Byte 1 Byte 2 Byte 3
DF
80
B0
DF
80
B1
DF
80
B2
DF
80
E0
DF
80
E0
DF
80
E1
DF
80
E1
DF
80
E1
DF
80
E1
104
Channel parameter block
Meaning
00
Number of the data record unknown
00
Length of the data record incorrect
00
Slot invalid or cannot be accessed.
01
Incorrect version
02
Error in the header information
01
Reserved bits are not 0.
02
Reserved bits are not 0.
05
Measuring range for voltage invalid.
20
Connection type invalid.
Solution
Enter a valid number for the data record.
Enter a valid value for the data record
length.
Check the station whether the module is
plugged or drawn.
Check the assigned values for the parame-
ters of the WRREC instruction
Check Byte 0. Enter valid values.
Check Bytes 1 and 2. Correct the length
and number of the parameter blocks.
Check Byte 10, 11, 14, 22, 30...34, 42,
50...54, 70...74 and set the reserved bits
back to 0.
Check Byte 8 and set the reserved bits
back to 0.
Check Byte 5. Permitted values: 01
0C
Check Byte 4. Permitted values: 00
0B
Analog input module AI Energy Meter 480VAC ST (6ES7134-6PA20-0BD0)
H
... 01
H
H
Manual, 12/2015, A5E36061895-AA
to
H
,
H