Siemens simatic et200sp Manual page 140

Modular i/o system with ip20 degree of protection
Hide thumbs Also See for simatic et200sp:
Table of Contents

Advertisement

User data variants
D.1 User data variants with 32 bytes input data / 12 bytes output data
Basic measured values L1L2L3 (ID 250 or FA
Table D- 6
Basic measured values L1L2L3
Byte
Allocation
0
User data variant
1
Quality information = QQ
2 ... 3
Current L1
4 ... 5
Current L2
6 ... 7
Current L3
8 ... 9
Voltage UL1-N
10 ... 11
Voltage UL2-N
12 ... 13
Voltage UL3-N
14 ... 15
Voltage UL1-UL2
16 ... 17
Voltage UL2-UL3
18 ... 19
Voltage UL3-UL1
20
Power factor L1
21
Power factor L2
22
Power factor L3
23
Total power factor L1L2L3
24
Scaling current L1
25
Scaling current L2
26
Scaling current L3
27
Scaling voltage UL1-N (UL1-UL2)
28
Scaling voltage UL2-N (UL2-UL3)
29
Scaling voltage UL3-N (UL3-UL1)
30 ... 31
Frequency
140
)
H
I
U
I
U
I
U
1
3
3
2
2
1
1
Analog input module AI Energy Meter 480VAC ST (6ES7134-6PA20-0BD0)
Data type
Unit
BYTE
-
BYTE
Bit string
UINT
1 mA
UINT
1 mA
UINT
1 mA
UINT
0.01 V
UINT
0.01 V
UINT
0.01 V
UINT
0.01 V
UINT
0.01 V
UINT
0.01 V
USINT
0.01
USINT
0.01
USINT
0.01
USINT
0.01
USINT
-
USINT
-
USINT
-
USINT
-
USINT
-
USINT
-
UINT
0.01 Hz
Value range
Measured
value ID
250 (FA
)
-
H
qq xx xx xx
-
0 ... 65535
66007
0 ... 65535
66008
0 ... 65535
66009
0 ... 65535
66001
0 ... 65535
66002
0 ... 65535
66003
0 ... 65535
66004
0 ... 65535
66005
0 ... 65535
66006
0 ... 100
66019
0 ... 100
66020
0 ... 100
66021
0 ... 100
66037
0 ... 255
-
0 ... 255
-
0 ... 255
-
0 ... 255
-
0 ... 255
-
0 ... 255
-
4500 ... 6500
66038
Manual, 12/2015, A5E36061895-AA

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents