Active power L1L2L3 (ID 253 or FD
Table D- 3
Active power L1L2L3
Byte
Allocation
0
User data variant
1
Quality information = QQ
2 ... 3
Current L1
4 ... 5
Current L2
6 ... 7
Current L3
8 ... 9
Active power L1
10 ... 11
Active power L2
12 ... 13
Active power L3
14 ... 15
Total active power L1L2L3
16 ... 19
Total active energy L1L2L3
20
Power factor L1
21
Power factor L2
22
Power factor L3
23
Total power factor L1L2L3
24
Scaling current L1
25
Scaling current L2
26
Scaling current L3
27
Scaling active power L1
28
Scaling active power L2
29
Scaling active power L3
30
Scaling active power L1L2L3
31
Scaling total active energy L1L2L3
Analog input module AI Energy Meter 480VAC ST (6ES7134-6PA20-0BD0)
Manual, 12/2015, A5E36061895-AA
D.1 User data variants with 32 bytes input data / 12 bytes output data
)
H
I
U
I
U
I
U
1
3
3
2
2
1
1
Data type
Unit
BYTE
-
BYTE
Bit string
UINT
1 mA
UINT
1 mA
UINT
1 mA
INT
1 W
INT
1 W
INT
1 W
INT
1 W
UDINT
1 Wh
USINT
0.01
USINT
0.01
USINT
0.01
USINT
0.01
USINT
-
USINT
-
USINT
-
USINT
-
USINT
-
USINT
-
USINT
-
USINT
-
User data variants
Value range
Measured
value ID
253 (FD
)
-
H
qq xx xx xx
-
0 ... 65535
66007
0 ... 65535
66008
0 ... 65535
66009
-27648 ... 27648
66013
-27648 ... 27648
66014
-27648 ... 27648
66015
-27648 ... 27648
66035
0 ...4294967295
225
0 ... 100
66019
0 ... 100
66020
0 ... 100
66021
0 ... 100
66037
0 ... 255
-
0 ... 255
-
0 ... 255
-
0 ... 255
-
0 ... 255
-
0 ... 255
-
0 ... 255
-
0 ... 255
-
137