User data variants
D.1 User data variants with 32 bytes input data / 12 bytes output data
Reactive power L1L2L3 (ID 252 or FC
Table D- 4
Reactive power L1L2L3
Byte
Allocation
0
User data variant
1
Quality information = QQ
2 ... 3
Current L1
4 ... 5
Current L2
6 ... 7
Current L3
8 ... 9
Reactive power L1
10 ... 11
Reactive power L2
12 ... 13
Reactive power L3
14 ... 15
Total reactive power L1L2L3
16 ... 19
Total reactive energy L1L2L3
20
Power factor L1
21
Power factor L2
22
Power factor L3
23
Total power factor L1L2L3
24
Scaling current L1
25
Scaling current L2
26
Scaling current L3
27
Scaling reactive power L1
28
Scaling reactive power L2
29
Scaling reactive power L3
30
Scaling reactive power L1L2L3
31
Scaling total reactive energy L1L2L3
138
)
H
I
U
I
U
I
U
1
3
3
2
2
1
1
Analog input module AI Energy Meter 480VAC ST (6ES7134-6PA20-0BD0)
Data type
Unit
BYTE
-
BYTE
Bit string
UINT
1 mA
UINT
1 mA
UINT
1 mA
INT
1 var
INT
1 var
INT
1 var
INT
1 var
UDINT
1 varh
USINT
0.01
USINT
0.01
USINT
0.01
USINT
0.01
USINT
-
USINT
-
USINT
-
USINT
-
USINT
-
USINT
-
USINT
-
USINT
-
Value range
Measured
value ID
252 (FC
)
-
H
qq xx xx xx
-
0 ... 65535
66007
0 ... 65535
66008
0 ... 65535
66009
-27648 ... 27648
66016
-27648 ... 27648
66017
-27648 ... 27648
66018
-27648 ... 27648
66036
0 ... 4294967295
226
0 ... 100
66019
0 ... 100
66020
0 ... 100
66021
0 ... 100
66037
0 ... 255
-
0 ... 255
-
0 ... 255
-
0 ... 255
-
0 ... 255
-
0 ... 255
-
0 ... 255
-
0 ... 255
-