Technical specifications
14.1 Technical specifications
Measuring range
•
•
Measuring inputs for voltage
•
•
•
•
•
•
•
•
•
•
Measuring inputs for current
•
•
•
•
•
•
•
•
94
Frequency measurement, min.
Frequency measurement, max.
Measurable line voltage between phase and
neutral conductor
Measurable line voltage between the line con-
ductors
Measurable line voltage between phase and
neutral conductor, min.
Measurable line voltage between phase and
neutral conductor, max.
Measurable line voltage between the line con-
ductors, min.
Measurable line voltage between the line con-
ductors, max.
Measuring category for voltage measurement
in accordance with IEC 61010-2-030
Internal resistance line conductor and N-
conductor
Power consumption, per phase
Surge voltage strength 1.2/50µs
Relative measurable current for AC, min.
Relative measurable current for AC, max.
Continuous current for AC, maximum permis-
sible
Apparent power consumption per phase for
measuring range 5 A
Rated value of short-time current carrying
capacity is restricted to 1 s
Input resistance measuring range 0 to 5 A
Zero point suppression
Impulse withstand capability
45 Hz
65 Hz
277 V
480 V
90 V
293 V
155 V
508 V
CAT II. CAT III with prescribed protective ele-
ments
3.4 mΩ
20 mW
1 kV
1%; in relation to the secondary rated current 5 A
100%; in relation to the secondary rated current 5
A
5 A
0.6 VA
100 A
25 mΩ; at the terminal
Configurable: 2 - 250 mA, default 50 mA
10 A; for 1 minute
Analog input module AI Energy Meter 480VAC ST (6ES7134-6PA20-0BD0)
6ES7134-6PA20-0BD0
Manual, 12/2015, A5E36061895-AA