Basic variables phase-specific measurement (ID 155 or 9B
Table D- 22
Basic variables phase-specific measurement L3
Byte
Allocation
0
User data variant
1
Quality information = QQ
2 ... 3
Current L3
4 ... 5
Voltage UL3-N
6 ... 7
Active power L3
8 ... 9
Reactive power L3
10 ... 11
Apparent power L3
12 ... 15
Active energy L3 total (inflow - outflow)
16 ... 19
Reactive energy L3 total (inflow - outflow)
20 ... 23
Apparent energy L3
24
Scaling current L3
25
Scaling active power L3
26
Scaling reactive power L3
27
Scaling apparent power L3
28
Scaling active energy L3 total (inflow - outflow)
29
Scaling reactive energy L3 total (inflow - outflow)
30
Scaling apparent energy L3
31
Power factor L3
Analog input module AI Energy Meter 480VAC ST (6ES7134-6PA20-0BD0)
Manual, 12/2015, A5E36061895-AA
D.1 User data variants with 32 bytes input data / 12 bytes output data
I
U
I
U
I
U
1
3
3
2
2
1
1
)
H
Data type
Unit
Value range
BYTE
-
155 (9B
BYTE
Bit string
qq xx xx xx
UINT
1 mA
0 ... 65535
UINT
0.01 V
0 ... 65535
INT
1 W
-27648 ... 27648
INT
1 var
-27648 ... 27648
INT
1 VA
-27648 ... 27648
UDINT
1 Wh
0 ... 4294967295
UDINT
1 varh
0 ... 4294967295
UDINT
1 VAh
0 ... 4294967295
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
0.01
0 ... 100
User data variants
Measured
value ID
)
-
H
-
66009
66003
66015
66018
66012
62315
62316
62314
-
-
-
-
-
-
-
66021
153

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents