Siemens simatic et200sp Manual page 152

Modular i/o system with ip20 degree of protection
Hide thumbs Also See for simatic et200sp:
Table of Contents

Advertisement

User data variants
D.1 User data variants with 32 bytes input data / 12 bytes output data
Basic variables phase-specific measurement (ID 156 or 9C
Table D- 21
Basic variables phase-specific measurement L2a
Byte
Allocation
0
User data variant
1
Quality information = QQ
2 ... 3
Current L2
4 ... 5
Voltage UL2-N
6 ... 7
Active power L2
8 ... 9
Reactive power L2
10 ... 11
Apparent power L2
12 ... 15
Active energy L2 total (inflow - outflow)
16 ... 19
Reactive energy L2 total (inflow - outflow)
20 ... 23
Apparent energy L2
24
Scaling current L2
25
Scaling active power L2
26
Scaling reactive power L2
27
Scaling apparent power L2
28
Scaling active energy L2 total (inflow - outflow)
29
Scaling reactive energy L2 total (inflow - outflow)
30
Scaling apparent energy L2
31
Scaling voltage UL2-N
152
I
U
I
U
I
U
1
3
3
2
2
1
1
Analog input module AI Energy Meter 480VAC ST (6ES7134-6PA20-0BD0)
)
H
Data type
Unit
Value range
BYTE
-
156 (9CH)
BYTE
Bit string
qq xx xx xx
UINT
1 mA
0 ... 65535
UINT
0.01 V
0 ... 65535
INT
1 W
-27648 ... 27648
INT
1 var
-27648 ... 27648
INT
1 VA
-27648 ... 27648
UDINT
1 Wh
0 ... 4294967295
UDINT
1 varh
0 ... 4294967295
UDINT
1 VAh
0 ... 4294967295
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
USINT
-
0 ... 255
Measured
value ID
-
-
66008
66002
66014
66017
66011
62215
62216
62214
-
-
-
-
-
-
-
-
Manual, 12/2015, A5E36061895-AA