Siemens simatic et200sp Manual page 141

Modular i/o system with ip20 degree of protection
Hide thumbs Also See for simatic et200sp:
Table of Contents

Advertisement

Total energy L1L2L3 (ID 249 or F9
Table D- 7
Total energy L1L2L3
Byte
Allocation
0
User data variant
1
Quality information = QQ
2
Reserved
3
Reserved
4 ... 7
Total active energy inflow L1L2L3
8 ... 11
Total active energy outflow L1L2L3
11 ... 15
Total reactive energy inflow L1L2L3
16 ... 19
Total reactive energy outflow L1L2L3
20 ... 23
Total apparent energy L1L2L3
24
Reserved
25
Scaling active energy, inflow
26
Scaling active energy, outflow
27
Scaling reactive energy, inflow
28
Scaling reactive energy, outflow
29
Scaling apparent energy
30
Reserved
31
Total power factor L1L2L3
Analog input module AI Energy Meter 480VAC ST (6ES7134-6PA20-0BD0)
Manual, 12/2015, A5E36061895-AA
D.1 User data variants with 32 bytes input data / 12 bytes output data
)
H
I
U
I
U
I
U
1
3
3
2
2
1
1
Data type
Unit
BYTE
-
BYTE
Bit string
BYTE
-
BYTE
-
UDINT
1 Wh
UDINT
1 Wh
UDINT
1 varh
UDINT
1 varh
UDINT
1 VAh
BYTE
-
USINT
-
USINT
-
USINT
-
USINT
-
USINT
-
BYTE
-
USINT
0.01
User data variants
Value range
Measured
value ID
249 (F9
)
-
H
qq xx xx xx
-
-
-
-
-
0 ... 4294967295
220
0 ... 4294967295
221
0 ... 4294967295
222
0 ... 4294967295
223
0 ... 4294967295
224
-
-
0 ... 255
-
0 ... 255
-
0 ... 255
-
0 ... 255
-
0 ... 255
-
-
-
0 ... 100
66037
141

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents