Energy counters
7.4 Resetting energy counters and overflow counters
3. Write the data record to the AI Energy Meter 480VAC ST module using the "WRREC"
instruction.
The input parameters must be allocated as follows:
– REQ: A new write job is triggered if REQ = TRUE.
– ID: Hardware identifier or start address of the Energy Meter (depending on the CPU
– INDEX: The data record number: 143
– LEN: The maximum length of the data record: 170
– RECORD: A pointer to the data area in the CPU which includes data record 143.
Note
If you want to write or read several AI Energy Meter 480VAC ST at the same time, keep
in mind the maximum number of active jobs in communication with SFB52/SFB53.
See also
Structure for energy counters (DS 143) (Page 55)