The optional ribbon cable terminal contacts the AS interface cable harness by means of penetration technology which
allows installation by "clipping in" the AS interface cable harness without cutting and without removing insulation.
Screw, 2x
Branch circuit M12
plug-in connector
Fig. 21:
Optional ribbon cable terminal for AS interface cable harness
AS interface electronics module - LED status displays:
LED status displays
"Power" and "Fault"
Fig. 22:
LED status displays on the AS-i electronics module
LED 1 "Power"
(green)
off
on
on
flashing
flashing
The central illuminated display flashes in the fault color (see Chapter "17.2. Blinking pattern & fault sig-
naling"), if the status LED 2 "Fault" is active.
50
LED 2 "Fault"
signalized status
(red)
off
Power OFF
on
No data traffic (expired Watchdog at slave address does not equal 0)
off
OK
on
Slave address = 0
flashing
Sensor supply overload / manual actuation activated / untaught / service/
maintenance request / PC service program service mode
English
Procedure:
Open the ribbon cable terminal
(loosen screws and remove cover)
Insert cable harness
Close ribbon cable terminal again
Tighten the screws
Loosen the thread-forming screws slightly and position
them on the existing threaded hole and screw in.