Control Head Type 8681
24VDC-Design
10.4.

Safety instructions

DANGER!
Danger of explosion in explosive atmosphere (only in the event of a fault as zone 2)!
• Opening the hood or the housing in an explosive atmosphere is only allowed in a not energized state!
WARNING!
Risk of injury due to electric shock!
• Before reaching into the system (except for the Teach-In procedure in a non-explosive atmosphere) switch off
the power supply and secure it to prevent restarting!
• Observe applicable accident prevention and safety regulations for electrical equipment!
• When setting the position measuring system (Teach-In), do not contact any live components!
Risk of injury from improper installation!
• Installation may be carried out by authorized technicians only and with the appropriate tools!
Risk of injury from unintentional activation of the system and uncontrolled restart!
• Secure system against unintentional activation.
• Following installation, ensure a controlled restart.
10.5.

Electrical installation / start-up

10.5.1. Cable gland with screw terminals

Procedure:
Open the housing following the instructions in Chapter "8. Opening and Closing the Housing".
Assemble connection cables for signals and power supply as well as for the external initiator where necessary
in observance of the rules of technology.
Insert cables through the respective cable glands into the interior of the housing.
Connect the wires to the connection terminals according to the connection configuration described in "Fig. 14".
If required, secure the cable with a cable clip!
Close the housing following the instructions in Chapter "8. Opening and Closing the Housing".
NOTE!
Ensure IP protection!
• To ensure IP protection, the union nuts of the cable glands must be tightened in accordance with the cable
sizes or dummy plugs used (approx. 1.5 Nm).
• If no external initiator is used, the right-hand connection opening must be tightly sealed using a dummy plug
or using a cable gland (SW 19, Ø 3 - 6 mm) with a dummy plug (Ø 5 - 6 mm)!