Design Aid - Burkert 8681 Operating Instructions Manual

Control head
Hide thumbs Also See for 8681:
Table of Contents

Advertisement

Control Head Type 8681
DeviceNet-Design
12.6.

Design aid

Power consumption of the electronics:
P
=
1.44 W
El
Power consumption of a valve during activation (200 ms):
P
=
1.0 W
Valve-ON
Power consumption of a valve after reduction:
P
=
0.6 W
Valve
Power consumption of an optical position report:
P
=
1.0 W
LED
Calculation examples:
Example 1:
3 valves are activated simultaneously, one position is reported (state for 200 ms):
P
=
P
Total
El
5.44 W
=
1.44 W
or
I
=
I
Total
El
228 mA =
60 mA
Example 2:
3 valves have been activated simultaneously, one position is reported (persistent state):
P
=
P
Total
El
4.24 W =
1.44 W
or
I
=
I
Total
El
177 mA =
60 mA
When using an external initiator, its power requirement should be added.
or
or
or
or
+ 3 x P
+ 1 x P
Valve-ON
+ 3 x 1.0 W
+ 1 x 1.0 W
+ 3 x I
+ 1 x I
Valve-ON
LED
+ 3 x 42 mA
+ 1 x 42 mA
+ 3 x P
+ 1 x P
Valve
+ 3 x 0.6 W
+ 1 x 1.0 W
+ 3 x I
+ 1 x I
Valve
LED
+ 3 x 25 mA
+ 1 x 42 mA
I
=
60 mA at 24 V
El
I
=
42 mA at 24 V
Valve-ON
I
=
25 mA at 24 V
Valve
I
=
42 mA at 24 V
LED
LED
LED
English
55