Electrical installation / start-up

DANGER!
Risk of injury due to electric shock (110 ... 130 V AC)!
• Before reaching into the system (except for the Teach-In procedure in a non-explosive atmosphere) switch off
the power supply and secure it to prevent restarting!
• Observe applicable accident prevention and safety regulations for electrical equipment!
• When setting the position measuring system (Teach-In), do not contact any live components!
Procedure:
Open the housing following the instructions in Chapter "8. Opening and Closing the Housing".
Assemble connection cables for signals and power supply as well as for the external initiator where necessary
in observance of the rules of technology.
Insert cables through the respective cable glands into the interior of the housing.
Connect the wires to the connection terminals according to the connection configuration described in "Fig.
31: 120 V AC electronics module". If required, secure the cable with a cable clip.
DANGER!
Risk of electric shock if the PE connection is not connected!
• the PE connection must be connected!
Clamp the protective conductor to the PE connection.
Check correct grounding.
Close the housing following the instructions in Chapter "8. Opening and Closing the Housing".
NOTE!
Ensure IP protection!
• To ensure IP protection, the union nuts of the cable glands must be tightened in accordance with the cable
sizes or dummy plugs used (approx. 1.5 Nm).
• If no external initiator is used, the right-hand connection opening must be tightly sealed using a dummy plug
or using a cable gland (SW 19, Ø 3 - 6 mm) with a dummy plug (Ø 5 - 6 mm)!
NOTE!
Use of the control head in explosive atmosphere
• Only use cables and cable glands which are approved for the respective application area and fit the cable
glands according to the respective operating instructions!
• Close all unnecessary openings with lock screws/plugs approved for explosions area!