4.8 Mounting the leakage
sensor
Fig. 19
Normally, the control valve is delivered with
positioner and leakage sensor already
mounted.
If the leakage sensor is mounted after the
valve has been installed or it is mounted on-
to another control valve, proceed as de-
scribed in following.
NOTICE
Risk of malfunction due to incorrect
fastening!
Fasten the leakage sensor using a
torque of 20 ±5 Nm.
Fig. 19: Mounting the leakage sensor
46
3
2
1
The M8 threaded connection on the NAMUR
rib should preferably be used to mount the
sensor (Fig. 19).
Tip:
If the positioner was mounted directly
onto the actuator (integral attach-
ment), the NAMUR interfaces on ei-
ther side of the valve yoke can be
used to mount the leakage sensor.
The start-up of the leakage sensor is de-
scribed in detail in the Operating Instructions
for EXPERTplus Valve Diagnostics
u EB 8389.
1 Leakage sensor
2 Screw
3 Plug connection