Advertisement

age the ribbon cable (between PCB and
display).
2. Use a knife to cut an opening at the
marked location (4).
3. Push the connector (11) with cable
through the opening and secure the prox-
imity switch (7) on the cover with a dot of
glue.
4. Insert the cable connector (11) at the
socket X7.
5. Guide the cable in such a manner that the
plastic cover can be placed back onto the
positioner. Insert the fixing screws (2) and
screw tight. Attach the clamping plate (8)
onto the proximity switch.
6. Attach the rotary switch (5). Make sure
the flattened side of the positioner shaft is
turned so that the rotary switch (5) can be
attached with the metal tag next to the
proximity switch.
7. On start-up of the positioner, set the op-
tion inductive alarm under Code 38 from
No to YES.
EB 8384-5 EN
Adjusting the limit switch
Socket X7 (11)
1
Cap
2
Screw
3
Rotary pushbutton
4
Marking
5
Rotary switch
Fig. 26: Retrofitting an inductive limit switch
7
9
Metal tag
6
Proximity switch
7
Clamping plate
8
9
Plastic cover
11 Connector