Note:
The binary inputs are configured in
the DI Function Blocks. Refer to
Configuration Manual
KH 8384-5.
u
 

3.2 Communication

The positioner is controlled completely by
digital signal transmission according to
™ fieldbus specification.
F
OUNDATION
Data are transmitted over the bus using digi-
tal, bit-synchronous Manchester coding at a
baud rate of 31.25 kbit/s over twisted-pair
wires according to IEC 61158-2.
Note:
If complex functions are started in the
positioner, which require a long cal-
culation time or lead to a large quan-
tity of data being saved in the vola-
tile memory of the positioner, the
alert 'busy' is issued over the DD.
This alert is not an error message
and can be simply confirmed.
Configuration and operation of the posi-
tioner over F
OUNDATION
scribed in the Configuration Manual
KH 8384-5.
u
 
3.2.1
Configuration using the
TROVIS-VIEW software
The positioner can be configured with
SAMSON's TROVIS-VIEW Configuration
and Operator Interface.
EB 8384-5
fieldbus are de-
Design and principle of operation
The positioner has for this purpose a serial
interface to allow the RS-232 or USB port of
a computer to be connected to it over an
adapter cable.
The TROVIS-VIEW software enables the user
to easily configure the positioner as well as
view process parameters online.
Note:
TROVIS-VIEW provides a uniform us-
er interface that allows users to con-
figure and parameterize various
SAMSON devices using device-spe-
cific database modules. The 3730-5
device module can be downloaded
free of charge from our website
(www. samson.de) at Services > Soft-
ware > TROVIS-VIEW. Further infor-
mation on TROVIS-VIEW (e.g. system
requirements) is available on our
website and in the Data Sheet
u T 6661.
3.2.2
Configuration using the
NI-FBUS™ configurator
The positioner can also be configured over
the NI-FBUS™ configurator from National
Instruments. For this purpose, an interface
card must be installed in a computer to con-
nect it to the F
OUNDATION
The integrated function blocks are linked us-
ing the NI-FBUS™ configurator.
™ fieldbus.