Attachment to the control valve – Mounting parts and accessories
4.7.3
Mounting the position
sensor to Type 3510 Mi-
cro-flow Valve
− Required mounting parts and accesso-
ries: Table 7 on page 52
Fig. 17
1. Place the lever (1) on the position sen-
sor in mid-position and hold it in place.
Unscrew the nut (1.1) and remove the
standard attached M lever (1) together
with the disk spring (1.2) from the sen-
sor shaft.
2. Screw the position sensor (20) onto the
bracket (21).
3. Select the S lever (1) from the accessories
and screw the follower pin (2) into the
1.1
1.2
20
21
Fig. 17: Mounting on a micro-flow valve
44
hole for pin position 17. Place the lever
(1) and disk spring (1.2) on the sensor
shaft. Place the lever in mid-position and
hold it in place. Screw on the nut (1.1).
4. Place follower clamp (3) on the valve
stem connector, align at a right angle
and screw tight.
5. Position the bracket (21) with the position
sensor on the valve yoke and screw tight,
making sure the follower pin (2) slides
into the groove of the follower clamp (3).
1
2
3
1
Lever
1.1
Nut
1.2
Disk spring
2
Follower pin
3
Follower clamp
20
Position sensor
21
Bracket
EB 8384-5 EN