Samson 3730-5 Mounting And Operating Instructions page 96

Electropneumatic positioner
Table of Contents

Advertisement

Code list
Error codes – Recommended
action
70
Calibration
Status classification
Recommended action Return positioner to SAMSON AG for repair.
71
General parameters Error in parameters not critical to control operation.
Status classification
Recommended action Confirm error. Check and, if necessary, change the settings of the re-
73
Internal device
error 1
Status classification
Recommended action Return positioner to SAMSON AG for repair.
74
FF parameters
Status classification
Recommended action Confirm error and perform a reset.
76
No emergency mode The travel measuring system of the positioner has a self-monitoring func-
Status classification
Recommended action Merely information, confirm, if necessary.
96
Condensed state message active. When prompted, Err appears.
When fault alarms exist, they are displayed here.
Error in data from production calibration. The positioner continues oper-
ation with cold start values.
[Maintenance required]
[Maintenance required]
quire parameters.
Internal device error
[Maintenance required]
Error in parameters not critical to control operation.
[Maintenance required]
tion (see Code 62).
An emergency mode (open-loop control) is not available for certain ac-
tuators, such as double-acting actuators. In case of a travel sensing er-
ror, the positioner vents the output (Output 38) or A1 in double-acting
actuators. During the initialization, the positioner automatically checks
whether the actuator has such a function or not.
[No message]
No further action required.
EB 8384-5 EN