Samson 3730-5 Mounting And Operating Instructions page 72

Electropneumatic positioner
Table of Contents

Advertisement

Start-up and settings
Deactivate travel limit:
Turn
 Code 11
Press
, Code 11 blinks.
g No
Turn
Press
.
Change pressure limit and control parame-
ters:
Note:
Do not change the pressure limit
(Code 16). Only change the control
parameters K
(Code 18) if the settings of the the re-
placed positioner are known.
Turn
 Code 16/17/18
72
Travel limit
Default: No
(Code 17) and T
P
V
Pressure limit
Default: No
K
level
P
Default 7
T
level
V
Default 2
, Code 16/17/18 blinks.
Press
Turn
to set the control parameter select-
ed.
Press
to confirm the setting.
Enter closing direction and blocking position:
mm
Turn
 Code 34
, Code 34 blinks.
Press
Turn
 Closing direction (CCL = counter-
clockwise/CL = clockwise)
Press
.
Turn
 Code 35
, Code 35 blinks.
Press
Turn
 Blocking position, e.g. 5 mm
(read off at travel indicator scale of the
blocked valve or measure with a ruler).
Set the fail-safe position:
Î Set switch for fail-safe position AIR TO
OPEN or AIR TO CLOSE according to
section 7.1.
Î Set volume restriction as described in
section 7.2.
Start initialization:
Î Press INIT key.
Closing direction (direction of ro-
tation causing the valve to move
to the CLOSED position (view on-
to positioner display)
Default: CCL (counterclockwise)
Blocking position
Default 0
EB 8384-5 EN