5 Installation

The work described in this section is only to
be performed by personnel appropriately
qualified to carry out such tasks.

5.1 Preparation for installation

Before mounting, make sure the following
conditions are met:
− The actuator is not damaged.
− The type designation, material and tem-
perature range of the actuator match the
ambient conditions (temperatures etc.).
See the 'Markings on the device' section
for nameplate details.
Proceed as follows:
Î Lay out the necessary material and tools
to have them ready during mounting.
Î Check that the vent plugs to be used are
not blocked.
Î Check any pressure gauges mounted on
valve accessories to make sure they func-
tion properly.
Î When the valve and actuator are al-
ready assembled, check the tightening
torques of the bolted joints. Components
may loosen during transport.

5.2 Mounting the device

See images in the 'Design and principle of
operation' section
Depending on the version, SAMSON control
valves are either delivered with the actuator
already mounted on the valve or the valve
and actuator are delivered separately. When
EB 8318 EN
delivered separately, the valve and actuator
must be assembled together on site. Proceed
as follows to mount the actuator and before
start-up.
WARNING
WARNING
!
!
Risk of personal injury due to exhaust air
being vented.
The actuator is operated with air. As a result,
air is vented during operation.
Î During mounting make sure that vent
openings are not located at eye level in
the work position of the control valve and
the actuator does not vent at eye level in
the work position.
Î Wear eye and hearing protection when
working near the actuator.
WARNING
WARNING
!
!
Crush hazard arising from the moving
actuator stem.
Î Do not touch the actuator stem or insert
hands or finger into the yoke while the
air supply is connected to the actuator.
Î Before working on the actuator,
disconnect and lock the pneumatic air
supply as well as the control signal.
Î Do not impede the movement of the
actuator stem by inserting objects into
the yoke.
Î Before unblocking the actuator stem after
it has become blocked (e.g. due to
seizing up after remaining in the same
position for a long time), release any
stored energy in the actuator (e.g. spring
compression). See 'Relieving the spring
Installation
5-1

Advertisement

Table of Contents
loading

This manual is also suitable for: