7.4 Limiting the signal pressure

If the maximum actuator force may cause
damage to the valve, the signal pressure
must be limited.
Enable configuration at the positioner before
limiting the signal pressure:
Note:
If no settings are entered within 120
seconds, the enabled configuration
function becomes invalid.
64
Reading direction for right
attachment of pneumatic
connections
Reading direction for left
attachment of pneumatic
connections
Enable configuration
Default: No
g Code 3, display: No
Turn
Press
, Code 3 blinks.
Turn
 YES
Press
, display:
Limit the signal pressure:
Turn
 Code 16
Press
, Code 16 blinks.
Turn
until the required pressure limit
(1.4/2.4/3.7 bar) appears.
Press
to confirm the pressure limit setting.
7.5 Checking the operating
range of the positioner
To check the mechanical attachment and the
proper functioning, the valve should be
moved through the operating range of the
positioner in the
manual set point.
Select
manual mode:
Turn
 Code 0
Press
, Code 0 blinks.
 MAN
Turn
Pressure limit
Default: No
manual mode with the
Operating mode
Default MAN
EB 8384-5 EN