Code list
Code
Parameter – Readings/
no.
values [default setting]
43 Firmware info control
44 y info
[0] to 100 %, 0P, MAX, – –
45 Solenoid valve info
YES, HIGH/LOW, No
46* Bus address
16 to 251, ESC
47* Write protection FF
YES, [No], ESC
48*
Diagnostic parameters u EB 8389
49*
90
Description
Read only
Indicates the positioner type and current firmware version in alter-
nating sequence.
Read only
Indicates the control signal y in % in relation to the travel range de-
termined during initialization.
MAX:
The positioner builds up its maximum output pressure, see
description in Code 14 and 15.
0P:
The positioner vents completely, see description in Code 14
and 15.
– – –:
The positioner is not initialized.
Read only
Indicates whether a solenoid valve is installed or not.
If a voltage supply is connected at the terminals of the installed sole-
noid valve, YES and HIGH appear on the display in alternating se-
quence. If a voltage supply is not connected (actuator vented, fail-
safe position indicated on the display by the S icon), YES and LOW
appear on the display in alternating sequence.
Bus address
16 to 247:
Positioners with fixed bus address
248 to 251: Positioners without fixed bus address (new or decom-
missioned positioners)
When write protection is active, device data can be read using FF
communication but not overwritten.
EB 8384-5 EN