2 HOLD : Applicable when unit is running
Event input close: Hold the profile
Event input open: Run profile again. Resume from the
segment where it hold earlier
3 ABOT: Applies when unit is in run mode
Requires only momentary type input
Event input close: Unit will abort the current running profile
and enter static mode.
4 MAN: Applies when unit is in static mode or run mode
Event input close: Outputs performs bumpless transfer
Event input open: Unit will perform normal PID operation
5 FTRA: Applies when unit is in static mode or run mode
Event input close: Performs failure transfer function
Event input open: Unit will perform normal PID operation
6 OFF: Applies when unit is in static mode or run mode
Event input close: All outputs/alarm turn off, profile stops
running
Event input open: If running, profile resumes where it was put
into off condition, outputs/alarms active again as per
configuration
7 PASS: Applies when unit is run mode
Requires only momentary type input to pass to next segment
Event input close: Profile will move ahead by 1 segment
8 PID2: Applies when unit is in static mode or run mode
If chosen, close the event input pins the PB2, TI2 and TD2 will
replace PB1, TI1 and TD1 for control.
UM0P411A
45-1