Igure 3.6 Deviation High Alarm 1 Operation - Brainchild P41 User Manual

Auto-tune fuzzy / pid profiling controller
Table of Contents

Advertisement

: A deviation high alarm alerts the operator when the process
deviates too high from set point value. When the process is higher
than SV+ASP1, a deviation high alarm occurs and the alarm is off as
the process is lower than SV+ASP1-A1HY. Figure 3.6 shows the
deviation high alarm operation.
Output 2 on
off
Output 2 on
off
Figure 3.6 Deviation high alarm 1 operation
Figure 3.6 Deviation high alarm 1 operation
: A deviation low alarm alerts the operator when the process
deviates too low from set point value. When the process is lower
than SV+ASP1 ( ASP1 is negative value ), a deviation low alarm
occurs, and the alarm is off as the process is higher than SV+ASP1+
A1HY. Figure 3.7 shows the deviation low alarm operation.
Process value
Output 2 on
off
Output 2 on
off
Figure 3.7 Deviation low alarm 1 operation
Figure 3.7 Deviation low alarm 1 operation
52
Process value
Alarm value
UM0P411A
SV+ASP1
SV+ASP1-A1HY
Alarm value
SV (set point value)
OUT2=ALM1
OUT2=rAL1
SV (set point value)
SV+ASP1+A1HY
SV+ASP1
OUT2=ALM1
OUT2=rAL1