Chapter 7 Modbus Communications
Chapter 7 Modbus Communications
This chapter specifies the Modbus Communications protocol as
RS-232 or RS-485 interface module is installed. Only RTU mode is
supported. Data is transmitted as eight-bit binary bytes with 1 start bit,
1 stop bit and optional parity checking (None, Even or Odd). Baud
rate may be set to 2400, 4800, 9600, 14400, 19200, 28800 and 38400.

7-1 Functions Supported

7-1 Functions Supported
Only function 03, 06 and 16 are available for this series of controllers.
The message formats for each function are described as follows:
Function 03: Read Holding Registers
Function 03: Read Holding Registers
Query ( from master )
Query
Slave address (1-247)
Function code (3)
Starting address of register Hi (0)
Starting address of register Lo (0-117,
No. of words Hi (0)
No. of words Lo (1-118)
CRC16 Hi
CRC16 Lo
Function 06: Preset single Register
Function 06: Preset single Register
Query
Query ( from master )
Slave address (1-247)
Function code (6)
Register address Hi (0)
Register address Lo (0-117, 128-143)
Data Hi
Data Lo
CRC16 Hi
CRC16 Lo
86
Response
Response ( from slave )
Byte count
Data 1 Hi
128-143)
Data 1 Lo
Data 2 Hi
Data 2 Lo
CRC16 Hi
CRC16 Lo
Response
Response ( from slave )